TM 11-6625-3081-23
7-37. TEMPERATURE SENSORS
7-37
INPUT CODE: AUGTEM (cont)
1 .
SEGMENT 10
1. VDT DISPLAY
TEMP CONTROLLER SOURCE C IN ERROR TEMPERATURE READS #.## AND SHOULD READ
35.00. PERFORM THE FOLLOWING REPLACE ACTIONS IN THE ORDER LISTED.
(REFERENCE TM 11-6625-3081-23 FOR REPLACEMENT PROCEDURES.)
REF. DES.
PART NO.
NAME
1. 1A1
13082765
CONTROL UNIT ASSY.
2. 2A3A1A17
13082974-29
SOURCE C
3. 2A3A1A17
13082165-19
SEC. HEAT SOURCE ASSY.
2. CORRECTIVE ACTION - SEGMENT 10
(a)
(b)
(c)
Remove Control Unit Assembly 1A1.
Check contacts of mating connectors
and repair if required.
Install replacement 1A1 and perform AUGTEM
test.
(It is not mandatory to perform hand held temperature probe
portion of test.) If AUGTEM test passes, no further action required.
If this segment displayed again, proceed to (b). If another segment
displayed, proceed to that segment and continue troubleshooting.
Remove Source C 2A3A1A17.
Check contacts of mating connectors and
repair if required.
Install replacement 2A3A1A17 and perform AUGTEM
test.
(It is not mandatory to perform hand held temperature probe
portion of test.)
If AUGTEM test passes, no further action required.
If this segment displayed again, proceed to (c). If another segment
displayed, proceed to that segment and continue troubleshooting.
.
Remove Secondary Heat Source 2A3A1A17. Check contacts of mating
connectors and repair if required.
Install replacement 2A3A1A17 and
perform AUGTEM test.
(It is not mandatory to perform hand held
temperature probe portion of test.) If AUGTEM test passes, no further
action required.
If this segment displayed again, proceed to (d). If
another segment displayed, proceed to that segment and continue
troubleshooting.
7-202
Change 2